Service Notice SN0027

Date: From: Subject:

November 2010

Capstone Technical Support

C65 and LCM-ICB Control Board SW v5.20 Release

Systems Affected

Capstone Model C65 MicroTurbine® systems running software lower than v5.xx through 5.1x. (high pressure gas).

Summary

Model C65 software has been upgraded to v5.20revA and is only to be installed in instances of nuisance faults (listed below) which cannot be resolved by steps outlined in the C65 Troubleshooting Guide (430013F and above). Along with this software upgrade, a LCM-ICB control board change will also be required.

Updates made to C65 software are detailed below:

Version 5.20revA Updates

 Resolved nuisance occurrences of the following LCM-ICB CPLD Watchdog faults: o 10021,ULCBIT

o 10058,CPLDWatchdogTimeout

o 10096,CPLDClockOutofTolerance

 Resolved nuisance occurrences of the following LCM-ICB SPI Communications faults:

o 10004,SPIERR o 10005,SPIData

 Resolved nuisance occurrences of the following LCM-ICB ADC Conversion faults: o 10002,ADCCONVFailure

o 10046,ADCStuck

450102 Rev B (November 2010) Page 1 of 3

This information is proprietary to Capstone Turbine Corporation. Neither this document nor the information contained herein shall be copied, disclosed to others, or used for any purposes other than the specific purpose for which this document was delivered. Capstone reserves the right to change or modify without notice, the design, the product specifications, and/or the contents of this document without incurring any obligation either with respect to equipment previously sold or in the process of construction. Copy is uncontrolled; user is responsible for verifying current revision.

Image | C65 and LCM-ICB Control Board SW v5.20 Release



c65-and-lcm-icb-control-board-sw-v520-release
Capstone Turbine For Sale - Microturbine C30 C65 C200 C600 C800 C1000 - Go to microturbine website

Search Engine Contact: greg@globalmicroturbine.com