SERIES 3000 FAULT CODES Sensor Faults

Series 3000 fault codes are assigned to sensor related faults. The following table shows the code number, fault description, system severity level (SSL) and the isolation message for each fault. The troubleshooting procedure for each message follows the table.

Fault No

Fault Description

SSL

Isolation Message

Comment

3000

TET1 OP

2

Internal Warning

3001

TET1 SH

2

Internal Warning

3002

TET2 OP

2

Internal Warning

3003

TET2 SH

2

Internal Warning

3004

BOTH TET

3

Internal Fault

3005

TET DELTA

2

Internal Warning

3006

TCIN OP

2

Internal Warning

3007

TCIN SH

2

Internal Warning

3008

TCIN HI TEMP

2

Hi-Temp Warning

3009

TCIN LO TEMP

2

Lo-Temp Warning

3010

FUEL TEMP OP

2

Internal Warning

Not Used

3011

SPARE TC 1 SH

2

Internal Warning

Not Used

3012

SPARE TC 2 OP

2

Internal Warning

Not Used

3013

SPARE TC 2 SH

2

Internal Warning

Not Used

3014

BOARD TEMP HI

3

Hi-Temp Fault

3015

BOARD TEMP LO

2

Lo-Temp Warning

3016

BOARD TEMP OP

3

Internal Fault

3017

BOARD TEMP SH

3

Internal Fault

3018

PWR SUPPLY HI

2

Internal Warning

3019

PWR SUPPLY LO

2

Internal Warning

3020

SPEED DELTA

3

Internal Fault

3021

PAMB FAILED

2

Internal Warning

3022

PAMB SH

2

Internal Warning

Not Used

3023

PAMB LOW

2

Hi-Alt Warning

3024

LO FUEL PRS

3

Internal Fault

Not Used

Continued on next page

Observe Safety Precautions - Refer to Safety Instructions for Details

430013-001 Rev A (October 2002) 35 Model C60 Troubleshooting Guide

This information is proprietary to Capstone Turbine Corporation. Neither this document nor the information contained herein shall be copied, disclosed to others, or used for any purposes other than the specific purpose for which this document was delivered. Capstone reserves the right to change or modify without notice, the design, the product specifications, and/or the contents of this document without incurring any obligation either with respect to equipment previously sold or in the process of construction.