Text | TA100 Natural Gas Robust power system achieves ultra-low emissions and reliable electricity from natural gas. | 001



TA100 Natural Gas

Robust power system achieves ultra-low emissions and reliable electricity from natural gas.

• Versatile applications in grid-connect, stand alone, or multiple unit arrays

• Fully-integrated CHP models available

• 100% step loading during operation

• Modular design affords con guration exibility and maximizes

balance of thermal and electrical needs

• Capable of performing for extended periods without the need

for a costly shutdown to perform maintenance

• Internal fuel gas compressor available for low fuel pressure

TA100

natural gas applications

Electrical Power Output Voltage

Electrical Service Frequency

System Net Output Current

Maximum Block Loading Electrical Ef ciency LHV

Fuel/Engine Characteristics(1)

NaturalGasHHV Inlet Pressure(3) Fuel Flow HHV Heat Rate LHV

Exhaust Characteristics(1)

Exhaust Gas Flow Exhaust Gas Temperature

105kW

400 – 480 VAC

4 wire

50/60 Hz

200A RMS per phase(2) 300A RMS neutral 100%

29.5%

High Pressure

36.4–44.6MJ/m3 (976–1195BTU/scf) 551– 655 kPa gauge (80 – 95 psig) 1,386 MJ/hr (1,314,500 BTU/hr) 11,380 BTU/kWh

High Pressure

0.84 kg/s (1.85 lbm/s) 302 ̊C (575 ̊F)

100kW

400 – 480 VAC

4 wire

50/60 Hz

200A RMS per phase(2) 300A RMS neutral 100%

28%

Onboard Gas Compressor Option

Electrical Performance(1) High Pressure Onboard Gas Compressor Option

36.4–44.6MJ/m3 (976–1195BTU/scf) 1.4 – 34.5 kPa gauge (0.2 – 5 psig) 1,386 MJ/hr (1,314,500 BTU/hr) 11,950 BTU/kWh

Onboard Gas Compressor Option

0.84 kg/s (1.85 lbm/s) 302 ̊C (575 ̊F)

Reliable power when and where you need it. Clean and simple.

Image | TA100 Natural Gas Robust power system achieves ultra-low emissions and reliable electricity from natural gas.



ta100-natural-gas-robust-power-system-achieves-ultra-low-emissions-and-reliable-electricity-from-natural-gas
Capstone Turbine For Sale - Microturbine C30 C65 C200 C600 C800 C1000 - Go to microturbine website

Search Engine Contact: greg@globalmicroturbine.com